收藏本站 嗨!欢迎来到虎朋网!

〖美乐柯〗LSLG系列螺杆冷水机组

AAA级 - 知名品牌品牌故事
  • 安徽美乐柯制冷空调设备有限公司

tp400-678-6559 / 021-51883031

选型列表
序号 采购操作
1
相关产品

 

Features:

● Twin screw compressor of world famous brand is employed,with high efficiency ,low noise level,. less wearing and long operation time.
● The unit is of high performance as they are made of the condensers and evaporators of grooved copper pipes,and high qualitycomponents,by specialized process.
● The unit is of easy to operate,and fridendly interfaced,as they employ leading brand of PLC,64k color touch screen and other controlelements.
● The energy saving for Multi-capacity regulation ,resulted in cost cut down for operation and maintenance.

Control system
● Lmaged system operation chart,showing the temperatures of water in and out ,the energy level of compressor run ,on/off button,run time,alarm etc.And the remote turn on/off function is available.PC remote control is optional.
● Notice for maintenance is indicated according to the accumulated run time of the compressor .it is a convenience to the maintenance man
● The control system will automatically balance the run time for each compressor for the mult-compressor unit

Safety protections
● Discharge check valve: it prevents the discharged gas from going back after the compressor stop.
● Phase lack protection: it protects the compressor for over high voltage ,voltage deficiency, and phase lack..
● Direction protection : it protects the compressor from damage resulted from Counter direction run.
● Oil heater : it heats the oil before the unit start ,keep the good lubrication for the unit before it runs.
● Overheat protection inside the motor of the compressor : it protect the compressor from burning down for too high coil temperature for overload, or abnormal run condition.
● High and low pressure protection : it protect the compressor and the system against extreme run condition and trouble.
● Freezing protection : it protects the unit from run without water flow.
● High temperature of chilled water protection : it works to protect the compressor in case the load is too large ; the temperature of the chilled water is ton high .it may result in compressor failure without this protect in the case.

Explanation:
1.Test Condition: Chilled water Tin/Tout: 12℃/7℃.Cooling water, Tin/Tout: 30℃/35℃;
2.Power supply:3P-380V-50Hz; Voltage Allowance:±10%, Phase Voltage Allowance:±2%;
3.The ;Data above is got by R22; Data for R134a,R407C etc are available on request;
4.There may be change of the dimensions without pre notice. For accurate you are welcome to ask us for installing drawing.